VCB ISM 12-24kV Specifications

TECHNICAL DATA

Type of ISM ISM15_LD ISM15_Shell ISM15_HD ISM25_LD ISM25_Shell
Rated voltage (Ur) ≤ 17.5 kV ≤ 17.5 kV ≤ 17.5 kV ≤ 24 kV ≤ 24 kV
Rated normal current (Ir) ≤ 1000 A ≤ 2000 A ≤ 3150 A ≤ 800 A ≤ 2000 A
Rated power frequency withstand voltage (Ud) 42 kV 42 kV 42 kV 50 kV 50 kV
Rated lightning impulse withstand voltage (Up) 95 kV 95 kV 95 kV 125 kV 125 kV
Rated short-circuit breaking current (Isc) ≤ 25 kA ≤ 31.5 kA ≤ 31.5 kA ≤ 20 kA ≤ 25 kA
Rated short-time withstand current (Ik) ≤ 65 kA ≤ 82 kA ≤ 82 kA ≤ 52 kA ≤ 64 kA
Rated short-time withstand current (Ik) ≤ 25 kA ≤ 31.5 kA ≤ 31.5 kA ≤ 20 kA ≤ 25 kA
Rated duration of short circuit (tk) 4 s
Rated frequency (fr) 50/60 Hz
Mechanical life (CO) 30,000 30,000 30,000 30,000 30,000
Rated breaking current operating sequence O-0.3s-CO-15s-CO